arXiv · 1403.7019
An internal model approach to (optimal) frequency regulation in power grids with time-varying voltages
Abstract
This paper studies the problem of frequency regulation in power grids under unknown and possible time-varying load changes, while minimizing the generation costs. We formulate this problem as an output agreement problem for distribution networks and address it using incremental passivity and distributed internal-model-based controllers. Incremental passivity enables a systematic approach to study convergence to the steady state with zero frequency deviation and to design the controller in the presence of time-varying voltages, whereas the internal-model principle is applied to tackle the uncertain nature of the loads.
Explore related subjects
Keep this discovery
Sebastian Trip, Mathias Bürger, Claudio De Persis. 2014-03-27. An internal model approach to (optimal) frequency regulation in power grids with time-varying voltages. https://arxiv.org/abs/1403.7019
Cite the original work for its findings. Save a collection to share your selection of sources.