arXiv · 2603.25167
Multi-Swing Transient Stability of Synchronous Generators and IBR Combined Generation Systems
Abstract
In traditional views, the build-up of accelerating energy during faults can cause the well-known first-swing angle instability in synchronous generators (SGs). Interestingly, this letter presents a new insight that the accumulation of decelerating energy due to the low voltage ride-through (LVRT) and recovery control of grid-following inverter-based resources (GFL-IBRs), might also result in transient angle instability in SGs. The transient energy accumulated during angle-decreasing swing transforms into the acceleration energy of the subsequent swing, hence such phenomena often manifest as multi-swing instability. Both theoretical analysis and simulation support these findings.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Songhao Yang, Bingfang Li, Zhiguo Hao, Yiwen Hu, Huan Xie, Tianqi Zhao, Baohui Zhang. 2026-03-26. Multi-Swing Transient Stability of Synchronous Generators and IBR Combined Generation Systems. https://arxiv.org/abs/2603.25167
Cite the original work for its findings. Save a collection to share your selection of sources.