Multivariable Geometric Laplace Transform and Fault Detection in Distributed-Converter Lines

Abstract

Monitoring a DC line with many distributed power converters is a genuinely spatio-temporal problem: the information about a localized fault travels along the whole conductor and reaches a few measurement points mixed with the dynamics of the line itself. This paper develops a two-dimensional geometric Laplace transform (t,x) -> (s_t,s_x) over a commutative subalgebra of the geometric algebra Cl(4,0), isomorphic to Segre's bicomplex numbers, in which two bivectors B_t and B_x act as independent imaginary units for the temporal and the spatial phase. Because the two phases live in algebraically distinguishable planes, a fault at position x_f leaves a transformed residual that factorizes as F_f(s_t) e^{-s_x x_f}: its temporal nature stays in the first factor and its location can be read as a geometric argument of the second. On this representation we build a transmission-line model of the converter line and its space-time dispersion relation, a distributed control by admittance shaping, including an exact treatment of discrete converter sites (spatial sampling, aliasing, and a per-converter droop realization that is exact on the sub-Nyquist band), and a fault diagnosis chain that detects, localizes and classifies injection-loss, shunt, sensor and local-controller faults, extends to multiple simultaneous faults with automatic order selection, and distinguishes the outage of a plant from a cable defect. As an integral object the transform is known in bicomplex analysis, and with a single independent variable it reduces to the complex Laplace transform; the contribution lies in its geometric embedding and in its operational use for fault diagnosis in distributed-converter networks. All results are reproduced by an accompanying open implementation.

Explore related subjects

Keep this discovery

BibTeXRIS

Francisco Manuel Arrabal-Campos, Francisco G. Montoya, Santiago Sánchez-Acevedo, Raymundo E. Torres-Olguin, Alfredo Alcayde. 2026-09-02. Multivariable Geometric Laplace Transform and Fault Detection in Distributed-Converter Lines. https://arxiv.org/abs/2609.02431

Cite the original work for its findings. Save a collection to share your selection of sources.

Discover connections

Connections use source metadata and explicit phrase matches, not verified experimental comparisons.

KEEP EXPLORING

Related papers

A simple derivation of the Kalman filter

In this lecture note, we present a concise and self-contained derivation of the discrete-time Kalman filter equations that requires only a basic understanding of least squares estimation. The treatment is designed to minimize mathematical overhead while preserving both rigor and generality.

math.OC

Constrained Parameter Update Law for Adaptive Control

In this paper, constrained parameter update laws for adaptive control are developed using barrier constraints. An interpretation of the parameter update law from a constrained optimization problem, in which a regularized Barrier saddle function is formulated to incorporate parameter constraints using inverse and logarithmic barrier functions from interior-point methods. The resulting constrained update law is integrated with an adaptive trajectory tracking controller, enabling online learning of the unknown system model parameters. Forward invariance of the parameter estimate is established and Lyapunov stability of the closed-loop system with the constrained parameter update law is derived. The effectiveness of the proposed constrained adaptive control law is demonstrated through simulations, which validate its ability to maintain parameter estimates within prescribed bounds while ensuring convergence to the true parameter values and achieving steady state tracking performance.

math.OC

A Closed-Loop Thermal Dynamic Model for AI Data Center Cooling Load Simulation

Cooling demand constitutes a significant and flexible component of AI data center electricity consumption, but time-synchronized measurements are scarce and constant coefficient-of-performance models cannot represent thermal dynamics. This letter proposes a closed-loop simulation model which couples a linear thermal dynamic model with deadband-based control to capture the nonlinear cooling dynamics. The model is validated using operational telemetry from the Marconi100 supercomputer. Compared with the baseline, the proposed model reduces the mean absolute error from 95.80 to 20.88~kW and the root-mean-square error from 109.79 to 27.27~kW. Evaluation over approximately 520 daily profiles further shows improved reproduction of daily peak demand and intraday variability. The proposed model provides a computationally tractable means of generating physically interpretable cooling load profiles for power system studies.

eess.SY