Kevin D. Jones

Publications and source records attributed to Kevin D. Jones.

5 recordsLinked to original sources

On PMU Adequacy for Wideband Dynamics Tracking Beyond Attenuation Assumptions

Recent work highlights the inadequacy of standard synchrophasors in capturing high-frequency grid dynamics, including data center oscillations, primarily due to filtering and windowing attenuation during phasor estimation. This letter shows how synchrophasor ambient data spectrum itself contains information on attenuation, which provides a way to identify critically impacted measurements and potentially estimate and undo the effect. Results are shown for synthetic data as well as actual synchrophasor estimates from digital fault recorders (DFRs) within the Dominion Energy system.

eess.SP↗

Does Synchrophasor Attenuation Preclude Detection of High-Frequency Oscillations?

Recent work suggests that standard synchrophasors are inadequate for capturing high-frequency data center oscillations, primarily due to filtering and windowing attenuation during phasor estimation. We prove that widely used periodogram and RMS energy detectors remain largely robust to it and confirm this by simulation.

eess.SP↗

Optimally Setting RMS Energy Bands for Detecting Oscillations

Oscillation monitors have root-mean-square (RMS) energy detectors at their core. These detect oscillation in a predefined frequency band by comparing the signal power in that band with a threshold (usually set empirically). A key design decision is the choice of frequency bands. Traditionally, for monitoring the stability of wide-area electromechanical modes, finer bands were set below 1 Hz, while higher frequencies were covered by wider bands. However, this approach can yield poor detection in modern power systems with fast and largely unknown local dynamics. This letter proposes an algorithm to set frequency bands from the ambient noise spectrum to maximize the average detection performance.

eess.SP↗

Identifying Oscillations Injected by Inverter-Based Solar Energy Sources

Inverter-based solar energy sources are becoming widely integrated into modern power systems. However, their impacts on the system in the frequency domain are rarely investigated at a higher frequency range than conventional electromechanical oscillations. This paper presents evidence of the emergence of an oscillation mode injected by inverter-based solar energy sources in Dominion Energy's service territory. This new mode was recognized from the analysis of real-world ambient synchrophasor and point-of-wave data. The analysis was performed by developing customized synchrophasor analysis tools deployed on the PredictiveGrid^{TM} platform implemented at Dominion Energy. Herein, we describe and illustrate the preliminary analysis results acquired from spectrogram observations, power spectral density plots, and mode shape estimation. The emergence and propagation of this new mode in Dominion Energy's footprint is illustrated using a heatmap based on a proposed frequency component energy metric, which helps to assess this oscillation's spread and impact.

eess.SP↗

Transmission Lines Positive Sequence Parameters Estimation and Instrument Transformers Calibration Based on PMU Measurement Error Model

Phasor Measurement Unit measurement data have been widely used in nowadays power system applications both in steady state and dynamic analysis. The performance of these applications running in utilities' energy management system depends heavily on an accurate positive sequence power system model. However, it is impractical to find this accurate model with transmission line parameters calculated directly with the PMU measurements due to ratio errors brought by instrument transformers and communication errors brought by PMUs. Therefore, a methodology is proposed in this paper to estimate the actual transmission lines parameters throughout the whole system and, at the same time, calibrate the corresponding instrument transformers. A PMU positive sequence measurement error model is proposed targeting at the aforementioned errors, which is applicable to both transposed and un-transposed transmission lines. A single line parameters estimation method is designed based on Least Squares Estimation and this error model. This method requires only one set of reference measurements and the accuracy can be propagated throughout the whole network along with the topology acquired by the introduced Edge-based Breadth-first Search algorithm. The IEEE 118-bus system and the Texas 2000-bus system are used to demonstrate the effectiveness and efficiency of the proposed method. The potential for deployment in reality is also discussed.

eess.SY↗