Search arXiv⌕ Search

arXiv subjects

Mazaher Karimi

Publications and source records attributed to Mazaher Karimi.

2 recordsLinked to original sources

Power Setpoint Tracking for Large-Scale EV Charging: Transformer-Constrained Charging Policy Learning with Self-Tuning Constraint Prices

In power setpoint tracking (PST), an operator follows a purchased charging profile without overloading shared transformers or undercharging vehicles. PST is cast as a constrained Markov decision process that minimizes tracking error subject to overload and mean user-satisfaction constraints. Transformer-Constrained Charging Policy Learning (TC-CPL) extends soft actor-critic with proportional-integral Lagrange-multiplier updates from measured violations, a residual on the incumbent dispatcher that is warm-started from its demonstrations, and a transformer-aware encoder shared by all ports. It observes no departure times or states of charge. Simulations (five seeds, 100 paired days) compare it with the incumbent, Round-Robin. On a 600-port, 122-substation district, raw overload falls from 3.59 to 0.0017 kWh/day (overloaded seed-days from 77% to 0.4%), and absolute tracking error falls by 27%. Delivered energy rises by 16%, and satisfaction rises from 0.959 to 0.989. On a 42-kW transformer with household load, overload falls from 1.86 to 0.0014 kWh/day and satisfaction rises from 0.974 to 0.985, but absolute tracking error is 22% higher. Against hand-set fixed multipliers, self-tuning is statistically indistinguishable on the district. On the single transformer, it raises satisfaction by 0.011 at similar overload, but a short sweep found a better-serving fixed pair. The overload multipliers stay below their cap.

cs.LG↗

Enhancing data security against cyberattacks in artificial intelligence based smartgrid systems with crypto agility

A new paradigm of electricity generation at the distribution level, with renewable and alternative sources, is possible with microgrids. The main idea is to have microgrids deployed on low- or medium-voltage active distribution networks. They can be advantageous in many different ways, such as improving the energy efficiency and reliability of the system and reducing transmission losses and network congestion. There are challenges in implementing MGs with DER units, those are related to power quality and stability issues voltage and fault level changes, energy management, low inertia, further complex protection schemes, load and generation forecasting, cyber-attacks, and cyber security. This paper shows the deep utilization of advanced, accurate, and fast methodologies such as artificial intelligence-based techniques. They guarantee efficient, optimal, safe, and reliable operation of smart grids safe against cyberattacks. AI refers to the computer-based system's ability to perform tasks with intelligence typically associated with human decision-making, they can learn from past experiences and solve problems.

eess.SY↗